ATI 9700 - Installation Guide (Initial Installation of the ATI 9700)

1.9 Connect Grounding

1.9.1 Overview

The primary ground for the ATI 9700 shelf is a grounding stud located on the right side of the chassis mounting
block (it will have the grounding symbol).

Note:

There is only one grounding procedure, since with the PEM8 (E002-C), the grounds are
combined.

1.9.2 Grounding Procedure

1.

Using a 6 AWG

grounding cable (green with yellow stripe), connect primary ground to the grounding stud

using two nuts or a lock washer and a nut (for two secured points). Connect the wire to the grounding stud
using a double crimp terminal (PANDUIT PMNF6-4R or equivalent). Refer to

Figure 1-16

.

FIGURE 1-16

Grounding stud exploded view

The separate protective earthing terminal provided on this product shall be permanently
connected to earth.

Grounding Stud

chassis

Grounding

stuf

nut

nut

crimped

connector

washer

washer

Grounding stud

exploded side view