1.9 Connect Grounding
1.9.1 Overview
The primary ground for the ATI 9700 shelf is a grounding stud located on the right side of the chassis mounting
block (it will have the grounding symbol).
Note:
There is only one grounding procedure, since with the PEM8 (E002-C), the grounds are
combined.
1.9.2 Grounding Procedure
1.
Using a 6 AWG
grounding cable (green with yellow stripe), connect primary ground to the grounding stud
using two nuts or a lock washer and a nut (for two secured points). Connect the wire to the grounding stud
using a double crimp terminal (PANDUIT PMNF6-4R or equivalent). Refer to
Figure 1-16
.
FIGURE 1-16
Grounding stud exploded view
The separate protective earthing terminal provided on this product shall be permanently
connected to earth.
Grounding Stud
chassis
Grounding
stuf
nut
nut
crimped
connector
washer
washer
Grounding stud