Wesley BC-620-4CA User Manual
Page 59
Curtis 1234/36/38 Manual,
OS
11
55
2 3 J U LY 2 0 0 8 D R A F T
3 — PROGRAMMABLE PARAMETERS:
Battery Parameters
BATTERY MENU
ALLOWABLE
PARAMETER
RANGE
DESCRIPTION
Nominal Voltage
24–84 V
Must be set to the vehicle’s nominal battery pack voltage. This parameter
Nominal_Voltage
1536–5376
is used in determining the overvoltage and undervoltage protection thresholds
for the electronic system.
Overvoltage protection cuts back regen braking to prevent damage
to batteries and other electrical system components due to overvoltage.
Undervoltage protection prevents systems from operating at voltages below
their design thresholds.
The four threshold points are calculated from the Nominal Voltage, Under-
voltage Cutback Range, User Overvoltage, and User Undervoltage parameter
settings and the controller’s minimum voltage and maximum voltage ratings:
VOLTAGE
RATINGS
BROWNOUT
MIN
MAX
CONTROLLER
VOLTAGE
*
VOLTAGE
VOLTAGE
24V
15V
16.8V
30V
24–36V
15V
16.8V
45V
36–48V
20V
25.2V
60V
48–80V
20V
33.6V
105V
80–108V
30V
50.4V
130V
Overvoltage = Either Max Voltage (see voltage ratings table)
or User Overvoltage × Nominal Voltage, whichever is lower.
Severe Overvoltage = Overvoltage (see previous item) + 10V.
Undervoltage = Either Min Voltage (see voltage ratings table)
or User Undervoltage × Nominal Voltage, whichever is higher.
Severe Undervoltage = Undervoltage point – Undervoltage Cutback Range.
* The Brownout Voltage is determined by the controller base type and cannot
be changed. When the capacitor voltage falls below the Brownout voltage
the bridge is switched off (i.e., motor current is switched off). If the capacitor
voltage stays below the Brownout voltage for > 64 msec the controller will reset
(equivalent to cycling the keyswitch). If the capacitor voltage rises above the
Brownout voltage before 64 msec have passed the bridge will be reenabled.
The Severe Undervoltage point can be set lower than the Brownout voltage.
Undervoltage Cutback Range 2.0–14.0 V
This parameter sets the voltage range between the Undervoltage and
Undervoltage_Cutback_Range
0–4096
Severe Undervoltage points (see Nominal Voltage description).
A Severe Undervoltage fault will be set if the capacitor voltage falls
below either the Severe Undervoltage point (drive current limit set to 0) or
the Brownout voltage (bridge disabled, motor current set to 0).
User Overvoltage
115–200 %
The value of this parameter is a percentage of the Nominal Voltage setting.
User_Overvoltage
293–512
The User Overvoltage parameter can be used to adjust the overvoltage
threshold, which is the voltage at which the controller will cut back regen
braking to prevent damage to the electrical system.
Typically this parameter is changed only when the controller is being
used in an application at the low end of the controller’s range: such as
a 48–80V controller being used in a system with a 48V battery pack. In
this case, the overvoltage threshold can be raised by setting the User
Overvoltage to a higher value. The overvoltage threshold can never be
raised above the controller’s power base maximum voltage rating.