Curtis 1234/36/38 Manual,
OS
11
7 — VCL
ENABLE_EMER_REV()
This function is used to engage emergency reverse using VCL. The 1311 EMR
Type must be set to = 1 in order for the Enable_Emer_Rev() function to operate.
If the system emergency reverse state is enabled (EMR_State bit variable = On),
the emergency reverse function will operate according to the Emergency Reverse
parameter settings; see page 59. To view the current emergency reverse state, see
the 1311 menu Monitor
»
Inputs: Emer Rev.
When the EMR_Type is set to = 1 and neither the Enable_Emer_Rev() nor the
Disable_Emer_Rev() function has been called, the state for emergency reverse is
Off (EMR_State bit variable = Off).
Syntax
Enable_Emer_Rev()
Parameters
None.
Returns
0 – Emergency reverse not enabled.
1 – Emergency reverse successfully enabled.
Error Codes
None.
Example
Enable_Emer_Rev()
This will enable the emergency reverse function.
DISABLE_EMER_REV()
This function is used to disengage emergency reverse using VCL. The 1311 EMR
Type must be set to = 1 in order for the Disable_Emer_Rev() function to operate.
If the system emergency reverse state is disabled (EMR_State bit variable = Off),
the emergency reverse function will stop operating and normal motor control func-
tion will resume (including an HPD/SRO check if the HPD/SRO Enable parameter
is set to On). To view the current emergency reverse state, see the 1311 menu
Monitor
»
Inputs: Emer Rev.
When the EMR_Type is set to = 1 and neither the Enable_Emer_Rev() nor the
Disable_Emer_Rev() function has been called, the state for emergency reverse is
Off (EMR_State bit variable = Off).
Syntax
Disable_Emer_Rev()
Parameters
None.
Returns
0 – Emergency reverse not disabled.
1 – Emergency reverse successfully disabled.
Error Codes
None.
Example
Disable_Emer_Rev()
This will disable the emergency reverse function.