3 — PROGRAMMABLE PARAMETERS:

EM Brake Control Parameters

EM BRAKE CONTROL MENU, cont’d

ALLOWABLE

PARAMETER

RANGE

DESCRIPTION

Set Speed Threshold

5–100 rpm

Determines the speed below which the EM brake will be commanded

Set_Speed_Threshold

5–100

to set. Setting this speed too high may cause a jerky stop when the EM
brake sets and stops the motor.

Release Delay

40–2000 msec Estimated time for the EM brake to physically release after the pull-in

EM_Brake_Release_Delay

5–250

voltage is applied. This is used to ensure the position hold torque buildup
is complete before the brake releases. When set too low, the vehicle may
experience rollback on EM brake release.

Set Speed Settling Time

0–5000 msec Determines how long the position hold function is allowed to operate

Set_Speed_Settling_Time

0–156

before the EM brake is set. This time should be set long enough for the
position hold to settle.

Note: This parameter is applicable only when Speed Mode or Speed

Mode Express is selected

and either Position Hold Enable = On or EM

Brake Type = 2.

Torque Preload Delay

0–800 msec

Estimated worst-case time to build up the torque required to hold the

EM_Brake_Torque_Preload_

0–100

vehicle stationary on a hill prior to EM brake release. This is used in

Delay

conjunction with Release Delay to determine when to release the brake
and allow the speed request to slew away from zero.

Note: This parameter is applicable only when Speed Mode or Speed

Mode Express is selected

and either Position Hold Enable = On or EM

Brake Type = 2.

Torque Preload Enable

On/Off

When enabled, this function eliminates rollback when the throttle is

EM_Brake_Torque_Preload_Enable On/Off

re-engaged on a ramp by forcing the vehicle to first enter position-hold

EM_Brake_Torque_Preload_

before setting the EM brake, and then “remembering” the amount of torque

Enable_Bit0 [Bit 0]

that was necessary to hold it on the ramp. When throttle is re-engaged,

this value is loaded in the motor before the EM brake is released. The
torque value is cleared automatically when KSI power is cycled.

Off = When a valid throttle input is received, the speed controller will

start with no torque preload as soon as the Release Delay expires. This will
allow some rollback when the EM brake releases.

On = When a valid throttle input is received, the speed controller will

start with a pre-set torque as measured by position-hold when the vehicle
came to a stop.

Note: This parameter is applicable only when Speed Mode or Speed

Mode Express is selected

and either Position Hold Enable = On or EM

Brake Type = 2.

Torque Preload Cancel Delay

0–120 sec

The timer starts after the EM brake is set. If the timer expires before the

EM_Brake_Torque_Preload_

0–15000

throttle is re-engaged, the torque preload memory will be cleared. Setting

Cancel_Delay

this parameter to zero disables the timer, i.e., the preload is never can-
celled. The purpose of this delay is to prevent the vehicle from lunging
forward if it is unloaded on a hill such that the torque measured by
position-hold is no longer valid.

Note: This parameter is applicable only when Torque Preload Enable =

On (see conditions above).