3 manual zero and span, 1 manually starting the zero/span sequence, 1 temperature control – Campbell Scientific CPEC200 Closed-Path Eddy-Covariance System User Manual
Page 45: Manual zero and span, Manually starting the zero/span sequence, Temperature control, 1. automatic zero/span sequence, On 6.3, N table, Table 6-1

CPEC200 Closed-Path Eddy-Covariance System
TABLE 6-1. Automatic Zero/Span Sequence
Step
Mode Status
Pump
valve_number
Duration (sec)
Keypad
Value
1
Measuring Pressure
Off
None
0
10
2
Checking CO2 Span 1
Off
CO2span1 2
SPAN_TIME
3
Checking Zero
Off
ZeroAir
1
ZERO_TIME
4
Setting Zero
Off
ZeroAir
1
10
5
Rechecking CO2 Span 1 Off
CO2span1 2
SPAN_TIME
6
Setting CO2 Span 1
Off
CO2span1 2
10
7
Checking CO2 Span 2
Off
CO2span2 3
SPAN_TIME
8
Checking CO2 Span 3
Off
CO2span3 4
SPAN_TIME
9
Checking CO2 Span 4
Off
CO2span4 5
SPAN_TIME
10
Equilibrating for EC
On
None
0
10
11
Switching to EC mode
On
None
0
0.1
6.3 Manual Zero and Span
There are two ways to manually zero/span the IRGA in the CPEC200:
1. The zero/span sequence may be run at any time by initiating the
sequence manually. This will often be the easiest way to do a manual
zero/span, but the sequence cannot do the H
2
O span. At the
completion of the sequence the system will automatically return to EC
mode.
2. The user may manually control each step in the zero/span process.
Using full manual control allows the H
2
O to be spanned. It also
bypasses some of the automated checking. For example, full manual
control will allow the user to do a zero or span even if there is a
diagnostic flag.
The two approaches to doing a manual zero/span are described below:
6.3.1 Manually starting the zero/span sequence
6.3.1.1 Temperature Control
Both the valve and scrub modules have heaters and fans to keep them within
their operating temperature range. Generally, this temperature control function
is disabled to conserve power. If the CPEC200 is configured for automatic
zero/span sequences, it will automatically enable temperature control of the
valve and scrub modules before the zero/span sequence is scheduled to begin.
This allows the valve module and scrub module to reach operating temperature
range even in very cold weather.
35