1. DISPLAY: 6 digit, 0.56" (14.2 mm) red sunlight readable or standard green

LED

2. POWER:

AC Versions:

AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA

Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working)

DC Versions:

DC Power: 11 to 36 VDC, 14 W

(derate operating temperature to 40° C if operating <15 VDC and three

plug-in option cards are installed)

AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA

Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).

3. SENSOR POWER: 12 VDC, ±10%, 100 mA max. Short circuit protected

4. KEYPAD: 3 programmable function keys, 5 keys total

5. USER INPUTS: Three programmable user inputs

Max. Continuous Input: 30 VDC

Isolation To Sensor Input Commons: Not isolated

Logic State: Jumper selectable for sink/source logic

Response Time: 6 msec. typical; function dependent. Certain resets, stores

and inhibits respond within 25 µsec if an edge occurs with the associated

counter or within 6 msec if no count edge occurs with the associated

counter. These functions include



,



,



,



,



,



, and



. Once activated, all functions are latched for

50 msec min. to 100 msec max. After that period, another edge/level may

be recognized.

6. MEMORY: Nonvolatile memory retains all programmable parameters and

display values when power is removed.

7. CERTIFICATIONS AND COMPLIANCES:

SAFETY

UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2

No. 61010-1

Recognized to U.S. and Canadian requirements under the Component

Recognition Program of Underwriters Laboratories, Inc.

UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

Type 4X Enclosure rating (Face only), UL50

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529

IP20 Enclosure rating (Rear of unit), IEC 529

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326:2006: Electrical Equipment for

Measurement, Control and Laboratory use.

Immunity to Industrial Locations:

Electrostatic discharge

EN 61000-4-2 Criterion A

4 kV contact discharge

8 kV air discharge

Electromagnetic RF fields EN 61000-4-3 Criterion A

10 V/m (80 MHz to 1 GHz)

3 V/m (1.4 GHz to 2 GHz)

1 V/m (2 GHz to 2.7 GHz)

Fast transients (burst)

EN 61000-4-4 Criterion A

2 kV power

1 kV I/O signal

2 kV I/O signal connected

to power

Surge

EN 61000-4-5 Criterion A

power 1 kV L to L, 2 kV L to G

signal 1 kV

RF conducted interference EN 61000-4-6 Criterion A

3 Vrms

Power freq magnetic fields EN 61000-4-8 Criterion A

30 A/m

AC power

EN 61000-4-11

Voltage dip

Criterion A

0% during 1 cycle

40% during 10/12 cycle

70% during 25/30 cycle

Short interruptions

Criterion C

0% during 250/300 cycles

Emissions:

Emissions

EN 55011

Class A

Notes:

1. Criterion A: Normal operation within specified limits.

2. Criterion C: Temporary loss of function where system reset occurs.

Refer to EMC Installation Guidelines section of the bulletin for additional

information.

8. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in

cards installed)

Storage Temperature Range: -40 to 60°C

Operating and Storage Humidity: 0 to 85% max. relative humidity non-

condensing

Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z

direction for 1.5 hours, 2 g.

Shock According to IEC 68-2-27: Operational 25 g (10 g relay), 11 msec in 3

directions.

Altitude: Up to 2000 meters

9. CONNECTIONS: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)

Wire Gage: 30-14 AWG copper wire

Torque: 4.5 inch-lbs (0.51 N-m) max.

10. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.

IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece

bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and

mounting clip included.

11. WEIGHT: 10.1 oz. (286 g)

V

IN

> 2.4 VDC

V

IN

< 0.9 VDC

Inactive

V

IN

< 0.9 VDC

V

IN

> 2.4 VDC

Active

SINKING INPUTS

5.1 K pull-up to +12 V

SOURCING INPUTS

5.1 K pull-down

INPUT STATE