PAXC & I: COUNTER AUTO RESET

PAXI & R: SETPOINT ON DELAY

PAXI & R: SETPOINT OFF DELAY

PAXI & R: SETPOINT HYSTERESIS

PAXC & I: SETPOINT ASSIGNMENT

21





SETPOINT ACTION



: When not using a setpoint, it should be set to



(no action).

For Counter Assignments:



With Timed Out action, the setpoint output activates when the

count value equals the setpoint value and deactivates after the

Time Out value. This action is not associated with Boundary types.



With boundary action, the setpoint output activates when the count

value is greater than or equal to (for



=



) or less than or equal

to (for



=



) the setpoint value. The setpoint output will

deactivate when the count value is less than (for



=



) or

greater than (for



=



) the setpoint value.



With Latch action, the setpoint output activates when the count

value equals the setpoint value. The output remains active until

reset. This action is not associated with Boundary types.

For Rate Assignments:



With Timed Out action, the setpoint output cycles when the rate

value is greater than or equal to (for



=



) or less than or equal

to (for



=



) the setpoint value. The Setpoint Time Out

(



) and Setpoint On Delay (



) values determine the

cycling times.



With Boundary action, the setpoint output activates when the rate

value is greater than or equal to (for



=



) or less than or equal

to (for



=



) the setpoint value. The setpoint output will

deactivate (Auto reset) as determined by the hysteresis value.



With Latch action, the setpoint output activates when the rate value

is equal to the setpoint value. The setpoint output remains active

until reset. If after reset, the rate value is greater than or equal to

(for



=



) or less than or equal to (for



=



) the setpoint

value, the output will reactivate.

 



Select the display that the setpoint is to be assigned.





SETPOINT VALUE

Enter the desired setpoint value. Setpoint values can also be entered in the

Quick Programming Mode when the setpoint is configured as



in Module 3.

(See Module 2 for Exchange Parameter Lists explanation.)





SETPOINT TRACKING

If a selection other than NO is chosen, then the value of the setpoint being

programmed (“n”) will track the entered selection’s value. Tracking means that

when the selection’s value is changed, the “n” setpoint value will also change

(or follow) by the same amount.





SETPOINT BOUNDARY TYPE



activates the output when the assigned display value (



) equals or

exceeds the setpoint value.



activates the setpoint when the assigned display

value is less than or equal to the setpoint.





SETPOINT STANDBY OPERATION

Selecting



will disable low acting setpoints at a power up until the display

value crosses into the alarm “off” area. Once in the alarm “off” area, the

setpoint will function according to the configured setpoint parameters.









 

 

 





to







 



















The hysteresis value is added to (for 

=



), or subtracted from (for 

=



), the setpoint value to determine at what value to deactivate the associated

setpoint output. Hysteresis is only available for setpoints assigned to the Rate

with boundary action.

to







This is the amount of time the Rate display must meet the setpoint

deactivation requirements (below hysteresis for high acting and above

hysteresis for low acting) before the setpoint’s output deactivates.



to



seconds





This is the amount of time the Rate display must meet the setpoint activation

requirements (below setpoint for 

=



and above setpoint for 

=



) before

the setpoint’s output activates. If the Rate Setpoint Action is Timed Out, this is

the amount of time the output is off during the on / off output cycling.



to



seconds





SETPOINT TIME OUT

If the setpoint action is Timed Out and the setpoint is assigned to Rate, then

this is the amount of time the output is on during the on / off output cycling. If

the setpoint action is Timed Out and the setpoint is assigned to Count, then this

is the amount of time the output will activate once the count value equals the

setpoint value.





This automatically resets the display value of the Setpoint Assignment

(



) counter each time the setpoint value is reached. This reset may be

different than the Counter’s Reset Action (x



) in Module 1 or 5.



to



seconds











SELECTION ACTION



No auto reset.



Reset to zero at the start of output activation.



Reset to count load value at the start of output activation.



Reset to zero at the end of output activation. (



action only).



Reset to count load value at the end of output activation. (



action only).