Surge protector, Leds, Specifications – Outback Power Systems FLEXpower ONE One Fully Pre-Wired Single Inverter System Installation Manual User Manual
Page 54

Specifications
52
900-0095-01-00 Rev A
Surge Protector
The FLEXware Surge Protector is designed to protect the FLEXpower ONE’s sensitive components 
from excessively high voltages (e.g., electrical storms). Thermally-fused metal oxide varistors (MOVs) 
limit (“clamp”) these voltages and transfer the resulting current to a lower-voltage 
port. The FLEXware Surge Protector features ACTIVE and ERROR LEDs for the DC, AC 
IN, and AC OUT circuits. The Surge Protector is located in the FLEXpower ONE’s AC 
wiring compartment. 
The FLEXware Surge Protector shunts 
excess current from: 
 DC+ (to
GROUND
)
 AC HOT IN
(to GROUND)
 AC NEUTRAL IN
(to GROUND)
 AC HOT OUT
(to AC
NEUTRAL
OUT)
 AC HOT OUT
(to GROUND)
 AC NEUTRAL OUT
(to GROUND)
LEDs
 ACTIVE LEDs are yellow. If these LEDs are on, power is present in that circuit.
It is normal for these LEDs to be on.
 ERROR LEDs are red. A red ERROR light indicates a problem. The LED means a
significant surge has damaged the FLEXware Surge Protector, and protection 
in that circuit is compromised. Although decreased protection remains, it is 
recommended that the FLEXware Surge Protector be replaced at this time, 
before further damage occurs. Further damage to the Surge Protector will 
eventually lead to damage to other FLEXpower ONE components. 
 For an ERROR LED to turn on, its circuit must be powered; its ACTIVE LED will
also glow. Note that if the circuit is not powered, the ERROR LED will not 
indicate a problem even if one is present. 
Specifications
Nominal 
Voltage 
Voltage 
Protection 
Max Surge 
Current 
Energy 
Rating 
Frequency
Protection 
Type 
Protected 
Circuit 
120-240 Vac 
12-48 Vdc 
390 Vac 
150 Vdc 
30 kA 
per circuit 
2500 Joules
50/60 Hz
Thermally 
Fused MOV 
x2 AC 
x1 DC 
Replacement Boards
Replacement boards for the Surge Protector are available in the event that a power surge damages 
the one currently installed. To obtain a replacement board, contact your local OutBack dealer. The 
OutBack designation for a replacement board is FW-SP-FP1. 