Operation

Selecting the AC Source and AC Input Limit on the Inverter

IMPORTANT:
The AC Input limit should NOT exceed the rating
of the overcurrent protection for the device.


DEC: Pressing this soft key decreases the value.

INC: Pressing this soft key increases the value.

AC2 GEN Menu:
Adjusts the maximum current the inverter will
draw from the generator for either supporting
loads or battery charging (between 2.0 Aac and
60.0 Aac).

AC1 GRID Menu:
Adjusts the maximum current the inverter will
draw from the grid for either supporting loads or
battery charging (between 5.0 Aac and 60.0 Aac).

The <Port> Soft Key switches between
ports on the HUB (i.e., between multiple
inverters if installed).

Figure 29

Inverter Setup Screen – Selecting AC Source

42