Installation

WARNING: Shock Hazard

Ensure there is only one Neutral-to-Ground Bond in the system. The
FLEXpower ONE comes with a Neutral-to-Ground Bond installed. If a Neutral-
to-Ground bond exists elsewhere in the system (e.g., in the main panel, or a
generator), the Neutral-to-Ground Bond in the FLEXpower ONE AC Enclosure
will need to be removed. See Figure 18. Check local code for specific
requirements.

AC Enclosure

Factory-installed

Neutral-To-Ground

Bond

Internal components shown may vary from model to model.

Factory wiring is not shown.

The factory-installed

Neutral-to-Ground Bond

must be removed if
another Neutral-to-
Ground Bond exists

elsewhere in the

configuration.

See Table 5 on page 32 for recommended
conductor sizes and torque requirements.

Figure 18

AC OUT Connections