beautypg.com

Wiring, Grounding, Table 3 – Outback Power Systems FLEXpower ONE One Fully Pre-Wired Single Inverter System Installation Manual User Manual

Page 28: Ground conductor size and torque requirements, Installation

background image

Installation

Wiring

IMPORTANT:

 All connections must comply with local electric code. Local code may

require sizes other than those recommended in this manual. For all wiring,
use copper conductors rated at 75°C minimum.

 If the installation involves grid-tie activities such as selling power back to

the grid, per NEC 690, ensure the total value of the breakers installed in
either the main AC distribution panel or the AC sub-panel does not exceed
the total rating on the terminal distribution bus in the distribution panel. In
other words, if the main terminal distribution bus in the panel is rated for
100 amps, then the total value of all the breakers installed can not exceed
100 amps.

 The size of the breaker installed to support the inverter should not exceed

60 A maximum.

 When smaller AC sources are used, smaller AC wiring may be used (down to

the minimum sizes indicated in Tables 4 and 6). The external AC breakers
must be sized accordingly to protect smaller wires.

Grounding

IMPORTANT:

 System grounding is the responsibility of the installer.
 Grounding requirements may vary by location depending on the local

electric code. In North America, inverter systems are considered two
separate electrical systems and, therefore, are required by code to have
each system (AC and DC) connected to a ground electrode conductor (also
known as a primary system ground).

 The AC and DC circuits are not bonded to the FLEXware enclosure.

 The equipment ground is marked with this symbol:

WARNING:

Ensure there is only one Neutral-to-Ground Bond in the system. The
FLEXpower ONE comes with a Neutral-to-Ground Bond installed. If a Neutral-
to-Ground bond exists elsewhere in the system, the Neutral-to-Ground Bond in
the FLEXpower ONE will need to be removed. See Figure 18. Check local code
for specific requirements.

Table 3

Ground Conductor Size and Torque Requirements

Terminal
Location

Minimum Allowed
Conductor Size

Maximum Conductor
Size

Torque
Requirements

Ground Bar

#12 AWG (3.3 mm

2

)

1/0 AWG (53.5 mm

2

)

35 in-lb (4 Nm)

26

900-0095-01-00 Rev A