To make the battery connections in a system without the FLEXnet DC Monitor:

1. Remove all hardware from the inverter’s battery negative (–) terminal post.

2. Place the Inverter Negative (–) cable lug and Charge Controller Negative (–) lug onto the terminal

post. Secure in place with the Flat Washer, Lock Washer and Nut. Torque to 50 in-lb (5.7 Nm).

3. Place the GFDI cable lug and Surge Protector DC Negative (–) cable lug onto the terminal post.

Secure in place with the next Lock Washer and Nut. Torque to 35 in-lb (4 Nm)

4. Connect the Battery (+) conductor to the DC Breaker lug closest to the Mounting Panel.

Torque to 50 in-lb (5.7 Nm).

5. Attach one end of the Battery Temperature Sensor (RTS) cable to the BATT TEMP port on the

Inverter and the other side to one of the batteries in the middle of the Battery Bank.

Internal components shown may vary from model to

model. Factory wiring is not shown.

900-0095-01-00 Rev A

29

Figure 15

Battery Connections without the FLEXnet DC

CAUTION: Equipment Damage
Ensure that correct polarity is
observed when connecting
battery cables.

Nut

Inverter
Battery (–)
Terminal Post

Flat Washer

Lock Washer

GFDI Lug

Surge

Protector

Lug

Charge

Controller

Battery (–)

Lug

See Table 4 on
page 27 for
conductor sizes
and torque
requirements.

Inverter
Battery (–)
Lug

Lock Washer

Nut

CAUTION: Equipment Damage
The Battery Negative lug must be the
first item installed on the inverter post.