Operation

Setting Battery Amp-Hours and Return Amps using the FLEXnet
DC Monitor

If a FLEXnet DC Monitor is installed in the configuration, the following parameters will need to be set.

 Battery Amp-Hours refers to the total amp-hour capacity of the battery bank (not just amp-hour

rating of the individual batteries within the battery bank).

 Return Amps is the low limit to which an absorption current must decrease, while still maintaining

the absorption voltage, before the battery is judged to be full. Use the battery manufacturer’s
specifications or 2% of the battery bank capacity.

IMPORTANT:

Access the Advanced Menu as

instructed on page 43.

To change Battery Amp-hours:
1. Press the <BAT> Soft Key.
2. Press the <INC> or <DEC> Soft

Key to change the parameter.

3. Press <ADV> to return to PG1.
4. Press <PG2> to advance to the

next setup page.


To change Return Amps:
1. Press the <CHARGE> Soft Key.
2. Press the <INC> or <DEC> Soft

Key to change the parameter.

3. Press <TOP> to return to PG2.
4. Press <PG3> to advance to the

next setup page.

5. Press <Main> to return to the

Main Screen.

44

900-0095-01-00 Rev A

Figure 31

Setting Battery Amp-hours and Return Amps