Figure 31, Setting battery amp-hours and return amps, Operation – Outback Power Systems FLEXpower ONE One Fully Pre-Wired Single Inverter System Installation Manual User Manual
Page 46: Important
Operation
Setting Battery Amp-Hours and Return Amps using the FLEXnet
DC Monitor
If a FLEXnet DC Monitor is installed in the configuration, the following parameters will need to be set.
Battery Amp-Hours refers to the total amp-hour capacity of the battery bank (not just amp-hour
rating of the individual batteries within the battery bank).
Return Amps is the low limit to which an absorption current must decrease, while still maintaining
the absorption voltage, before the battery is judged to be full. Use the battery manufacturer’s
specifications or 2% of the battery bank capacity.
IMPORTANT:
Access the Advanced Menu as
instructed on page 43.
To change Battery Amp-hours:
1. Press the <BAT> Soft Key.
2. Press the <INC> or <DEC> Soft
Key to change the parameter.
3. Press <ADV> to return to PG1.
4. Press <PG2> to advance to the
next setup page.
To change Return Amps:
1. Press the <CHARGE> Soft Key.
2. Press the <INC> or <DEC> Soft
Key to change the parameter.
3. Press <TOP> to return to PG2.
4. Press <PG3> to advance to the
next setup page.
5. Press <Main> to return to the
Main Screen.
44
900-0095-01-00 Rev A
Figure 31
Setting Battery Amp-hours and Return Amps