Dc connections, Table 4, Dc conductor size and torque requirements – Outback Power Systems FLEXpower ONE One Fully Pre-Wired Single Inverter System Installation Manual User Manual

Page 29: Figure 13, Ground connections, Installation

background image

Installation

Figure

13

Ground

Connections

DC Connections

Table 4

DC Conductor Size and Torque Requirements

DC Terminal

Minimum Allowed
Conductor Size

Maximum
Conductor Size

Torque
Requirements

Breaker
Size

Battery Positive (+)

2/0 AWG (67.5mm

2

)

N/A (ring terminal)

50 in-lb (5.7 Nm)

175 Adc

Battery Negative (–)
(Shunt)

2/0 AWG (67.5 mm

2

)

N/A (ring terminal)

50 in-lb (5.7 Nm)

N/A

PV Positive (+)

#4 AWG (21.2 mm

2

)

#2 AWG (33.6 mm

2

)

35 in-lb (4 Nm)

80 Adc

PV Negative (–)

#4 AWG (21.2 mm

2

)

#2 AWG (33.6 mm

2

)

35 in-lb (4 Nm)

N/A

Ground Bus Bar

#12 AWG (3.3 mm

2

)

1/0 AWG (53.5 mm

2

)

35 in-lb (4 Nm)

N/A


 To make the battery connections in systems that have the FLEXnet DC Monitor, see Figure 14 on

page 28.

 To make the battery connections in systems that do not have the FLEXnet DC Monitor, see Figure

15 on page 29.

To make the PV connections, see Figure 16 on page 30.

900-0095-01-00 Rev A

27