AC Connections

WARNING: Fire Hazard

Multi-wire branch circuits in residential installations can create a potential fire
hazard with inverter installations. Be sure to check for multi-wire branch circuits
before making any AC connections and make any changes required to remove
the hazard.

Table 5

AC Conductor Size and Torque Requirements

AC Terminal

Minimum Allowed
Conductor Size

Maximum
Conductor Size

Torque
Requirements

Breaker
Size

AC IN

#14 AWG (2.1 mm

2

)

1/0 AWG (53.5 mm

2

)

35 in-lb (4 Nm)

60 Aac

AC OUT

#14 AWG (2.1 mm

2

)

1/0 AWG (53.5 mm

2

)

35 in-lb (4 Nm)

60 Aac

Neutral Bus Bar

#14 AWG (2.1 mm

2

)

1/0 AWG (53.5 mm

2

)

35 in-lb (4 Nm)

N/A

Internal components shown may vary from model to model.

Factory wiring is not shown.

See Table 5 for recommended conductor

sizes and torque requirements.

1

See the WARNING on

page 32 for additional

information.

Neutral-to-Ground

Bond

1

Figure 17

AC IN Connections

900-0095-01-00 Rev A