Rack ac power distribution, Rack pdm – HP 3000 Enterprise Virtual Array User Manual

Page 80

background image

0131a

1

2

3

Figure 26 Rack PDM

1. Power receptacles

2. Thermal circuit breakers

3. AC power connector

Rack AC power distribution

The power distribution in an Enterprise Virtual Array rack is the same for all variants. The site AC input

voltage is routed to the dual PDU assembly mounted in the rack lower rear. Each PDU distributes AC to a

maximum of four PDMs mounted on the left and right vertical rails (see

Figure 27

).

PDMs 1 through 3 connect to receptacles A through D on PDU 1. Power cords connect these

PDMs to the number 1 drive enclosure power supplies and to the upper controller enclosure.

PDMs 4 through 6 connect to receptacles A through D on PDU 2. Power cords connect these

PDMs to the number 2 drive enclosure power supplies and to the lower controller enclosure.

NOTE:

The locations of the PDUs and the PDMs are the same in all racks.

80

Enterprise Virtual Array hardware components