En.02 unrecoverable condition—power supply missing, Power supply element numbering – HP 3000 Enterprise Virtual Array User Manual

Page 123

background image

CXO7952A

2

1

Figure 47 Power supply element numbering

The following sections define the power supply condition reports.

0.2.en.01 NONCRITICAL Condition—Power supply AC input missing

The loss of the AC input to a power supply makes the remaining power supply a single point of failure.
This condition report remains active until AC power is applied to the power supply.
Complete the following procedure to correct this problem:

1.

Record all six characters of the condition report.

2.

Ensure that there is AC power to the rack PDU, and from the PDU to the PDMs and that the PDU and

PDM circuit breakers are not reset.
If there is no AC power to the PDU, contact building facilities management.
Verify that the power supply AC power cord is properly connected.

3.

If AC is present, and the rack power distribution circuitry is functioning properly, the power supply

indicator should be on.

4.

Observe the EMU to ensure the error is corrected.

5.

Contact your authorized service representative.

0.2.en.02 UNRECOVERABLE condition—Power supply missing

This condition report indicates a power supply is not installed or installed incorrectly. Both of these

conditions affect air flow within the enclosure and can cause an overtemperature condition. Enclosure

shutdown is imminent.
The operational power supply will automatically shut down after seven minutes, thereby disabling the

enclosure. This condition report remains active until either the problem is corrected, or the operational

power supply shuts down, whichever occurs first.
To correct this problem, record all six characters of the condition report, then contact your authorized

service representative.

CAUTION:

Removing power from an enclosure may cause the loss or corruption of data. To avoid this condition, shut

down the system using HP Command View EVA. An automatic shutdown and possible data corruption

may result if the power supply is removed before a replacement is available.

0.2.en.03 CRITICAL condition—Power supply load unbalanced

This condition report indicates that a component within a power supply may have failed. This can make

the remaining power supply a single point of failure.
This condition report remains active until corrected.
Complete the following procedure to correct this problem:

1.

Record all six characters of the condition report.

HP StorageWorks 3000/5000 Enterprise Virtual Array user guide (VCS 4.xxx)