Information – NORD Drivesystems BU0040 User Manual
Page 50
NORDAC Control and Parameter Boxes
50
Subject to technical alterations
BU 0040 GB-0113
3.1.3.3 Operating mode IO-S (Setpoint mode via DI1 of the frequency inverter)
In the operating mode IO-S, communication is via digital input "1" of the frequency inverter. The frequency inverter
does not return any operating or parameter values to the box.
Field of use
In this operating mode the box can communicate with SK 2xxE series frequency inverters.
Functions
In this operating mode the functions
Control
Setpoint display
are available. The setpoint display is scaleable, the setpoint value is continuously transferred to the frequency
inverter.
Connections
Connection to the horizontal terminal bar is by means of a
3-wire cable.
Settings on the frequency inverter
Name
Parameter number
Value
Notes
Function, setpoint input
P400 [-05]
{01}*
Corresponds to default value
Function of digital input 1
P420 [-01]
{29}**
The function {29} "Enable Setpoint Box" must be
previously set with the aid of a parameterisation
tool or in the IO-C mode.
*
The function can be re-parameterised as required (e.g. as an auxiliary setpoint ("Frequency addition")). For this, the SK SSX-3A must temporarily be set to IO-C mode, or a different
parameterisation tool (e.g. NORD CON, ParameterBox etc.) must be used.
**
The control commands from the Simple Setpoint Box (Enable/Stop) are only processed by the frequency inverter with this setting.
Information
Deactivation of the IO functions
In "IO-S" mode the parameterised functions of Digital Input 1 (parameter (P420[-01])) are deactivated.
The DIP switch S1:
3 … 5 of the frequency inverter ("BUS" / "IO") must be left in the factory setting ("OFF" or"0")
in order to prevent communication faults on the frequency inverter.
24V
GND/0V
44
40
B1
C1
24V voltage supply from SK 2xxE
b)
I/O connection for FI setpoint values
OUT
Connection for IO-S mode
SK SSX-3A
SK 2xxE-
44
40
21
1
a) If available on the frequency inverter
b) Supply via terminal 43 or 44, according to the device 24V
DC
– Supply by separate mains unit is also possible
c) Observe correct voltage (24V
DC
), if necessary, provide the supply voltage to the SK SSX3A separately.
44
24V
DC
40
GND
B1
Signal OUT
C1
Signal IN