NORD Drivesystems BU0040 User Manual
Page 38
NORDAC Control and Parameter Boxes
38
Subject to technical alterations
BU 0040 GB-0113
Parameter
Setting value / Description / Note
P1306
Box password
0 ... 9999
[ 0 ]
If the password function is to be reset, the password selected in the >Set Password< parameter
must be entered here. If the correct password has been selected, than all functions of the
ParameterBox can be used again.
NOTE: In case the password is not known and parameterisation of the inverter needs to be
carried out, please contact our Technical Support.
P1307
Reset Box parameter
Start, Off
[Off]
In this parameter the ParameterBox can be reset to the default setting. All ParameterBox settings
and the data in the storage media will be deleted.
P1308
NORDAC p-box
Version ...
R …
[ … ]
Displays the software version of the ParameterBox. Please keep to hand.
2.2.3
Table of possible error messages
The following describes all possible error messages of the ParameterBox. Error messages which relate to the
connected frequency inverter (E xx.x) are described in the frequency inverter manual or one of the relevant
supplementary instructions.
Display
Error number
Fault
Text in the ParameterBox
Cause
Remedy
Communication error
200
Illegal parameter number
These error messages are due to EMC interference or differing software
versions of the participants.
Check the software version of the ParameterBox and that of the
connected frequency inverter.
Check the cabling of all components, regarding possible EMC
interference
Plug-in EEPROM on the frequency inverter (Memory module)
not recognised (Error: 201) Check for firm connection
201
Parameter value cannot be changed
202
Parameter value out of range
203
Faulty SUB Index
204
No Array parameter
205
Incorrect parameter type
206
Incorrect response identifier
USS interface
207
Checksum error of
USS interface
Communication between frequency inverter and ParameterBox is faulty
(EMC), safe operation cannot be guaranteed.
Check the connection to the frequency inverter. Use a shielded
cable between the devices. Route the BUS leads separately from
the motor cables.
208
Incorrect status identifier
USS interface
Communication between frequency inverter and ParameterBox is faulty
(EMC), safe operation cannot be guaranteed.
Check the connection to the frequency inverter.
Use a shielded cable between the devices. Route the BUS leads
separately from the motor cables.
209
Inverter not responding
The ParameterBox is waiting for a response from the connected frequency
inverter. The waiting time has elapsed without a response being received.
Check the connection to the frequency inverter.
The settings of the USS parameters for the frequency inverter
were changed during operation.