2 Parameter Boxes
– Installation
BU 0040 GB-0113
Subject to technical alterations
19
2.1.5
SK TU3-
… – (only for SK 5xxE)
2.1.5.1 ControlBox SK TU3-CTR
The SK TU3-CTR ControlBox is used for the commissioning,
configuration and control of the SK 5xxE frequency inverter. It
is mounted directly on the slot for the technology units.
Communication with the inverter and the power supply of the
module are provided by a contact strip The module cannot be
used independently from the inverter.
The display is via a 4-digit, 7-segment display. Control is via 6
control buttons.
The parameters of an inverter can be saved.
2.1.5.2 ParameterBox SK TU3-PAR
The
SK TU3-PAR
ParameterBox
is
used
for
the
commissioning, configuration and control of the SK 5xxE
frequency inverter. It is mounted directly on the slot for the
technology units. Communication with the inverter and the
power supply of the module are provided by a contact strip
The module cannot be used independently from the inverter.
The display is via a 4-line LED display. Control is via 8 control
buttons.
The parameters of 5 inverters can be saved.
2.1.5.3 Installing the technology unit
Modules must not be inserted or removed unless the device is free of voltage. The slots may only be used for the
intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the
frequency inverter.
The Installation of the technology units must be carried out as follows:
1. Switch off the mains voltage, observe the
waiting period.
2. Push the control terminals cover down
slightly or remove.
3. Remove the blank cover, by releasing the
catch at the lower edge and turning it
upwards.
4. Hook the technology unit onto the upper
edge slots and press in lightly until it
engages. Ensure full contact with the
connector strip and fasten with the screws if
necessary.
5. Close the control terminal cover again.