NORD Drivesystems BU0040 User Manual
Page 22
NORDAC Control and Parameter Boxes
22
Subject to technical alterations
BU 0040 GB-0113
Control with the SimpleBox / ControlBox
The frequency inverter can only be controlled via the SimpleBox, if it has not previously been enabled via the
control terminals or via a serial interface (P509 = 0 and P510 = 0).
As well as this, with the series SK 500E and SK 700E no technology unit (SK TU3-PAR or SK TU1-PAR) may be
plugged into the inverter.
If the "START" key is pressed, the frequency inverter in the operating display changes (selection P001). The
frequency inverter supplies 0Hz or the minimum frequency (P104) or jog frequency (P113) which has been set.
The following illustration is for the SimpleBox and applies accordingly for the ControlBox.
Parameter set display:
The LEDs indicate the actual operating parameter set in the operating display (P000) and the current parameter set
being parameterised (
P000). In this case, the display appears in binary form.
The parameter set can also be changed during operation via the parameter P100 (control via SimpleBox).
Frequency setpoint:
The current frequency setpoint depends on the setting in the parameters jog frequency (P113) and minimum
frequency (P104). This value can be altered during keyboard operation with the value keys
and
permanently
stored in P113 as the jog frequency by pressing the ENTER key.
Frequency addition (only SK 5xxE):
If the parameter “PotentiometerBox Function” (P549) has been set to function {4}”Frequency addition” or function
{5} “Frequency subtraction”, as of software version 1.7 of the inverter a setpoint can be added via the Box, even if
enabling and other setpoints are provided from another source (control terminals, BUS).
However, after the drive unit has been shut down, this additive setpoint is reset to zero.
By pressing the ENTER key however, the set value is permanently stored in parameter P113 as the jog frequency,
and continues to be available as a setpoint value on re-enabling after shutdown.
Emergency stop (only SK TU3-CTR):
By simultaneously pressing the STOP key
and the "Change direction key”
, an emergency stop can be
initiated.
Information for the SimpleBox (SK CSX-3x)
No technology unit (SK TUx-PAR) may be plugged in if SK 500E and SK 700E series inverters are used.
Otherwise, communication errors can be expected.
P1
P2
NORD
DRIVESYSTEMS
OK
SK CSX-3H
STOP
(no enable)
START
(enable)
Rotation
direction reversal
Store current
frequency
Increase / decrease the
frequency, or set it to "0" if
simultaneously pressed
Parameter set display
P set No..
P1
P2
1
Off
Off
2
On
Off
3
Off
On
4
On
On