Combinations of binary outputs and inputs 5.16

Limit switches 5.17

Fct. 3.07 HARDWARE
Press

key.

Define function of terminal B1,

press key

PULSOUTP.

(= pulse output)

Select with key

,

STATUSOUTP.

(= status output)

press key

to advance to

CONTROLINP.

(= control input)

terminal B2.

Define function of terminal B2,

press key

STATUSOUTP.

(status output)

Select with key

.

CONTROLINP.

(control input)

Press key

to return to Fct. 3.07 HARDWARE.

Please note: If, for example, both output terminals (B1 and B2) are set to status output,

or to control input, their operating modes can ony be selected once.

Example: B1 and B2 are status outputs.
If status output B1 is used for the automatic range change BA, this operating mode
is not available for status output B2.

}

}

Fct. 1.06 or 1.07 status outputs B1 or B2
(Define operating mode of output terminals, see Sect. 5.16)
Press key

.

Set status output B1 or B2 to “TRIP POINT” by pressing key

(1 to 9 times).

Press

key to transfer to number setting, 1st digit (cursor) flashes.

Change flashing digit with key

, use key

to shift cursor 1 place to the right.

Display XXX – YYY

Setting ranges:

XXX value = 0 – 150% of Q

100%

YYY value = 0 – 150% of Q

100%

Hysteresis

1% (= difference between XXX and YYY values)

Switching performance (N/O or N/C contact) can be set.

Note:

When the two status outputs B1 and B2 are activated (see Sect. 5.16),
min. and max. values can, for example, be signalled.
The limit switches are active only in the case of forward flow.

N/O contact XXX value > YYY value
Contact closes
when flowrate greater than XXX value

Example: XXX = 55%

YYY = 45%
Hysteresis = 10%

N/C contact XXX value < YYY value
Contact opens
when flowrate greater than YYY value

Example: XXX = 45%

YYY = 55%
Hysteresis = 10%

YYY XXX

XXX YYY

hysteresis

hysteresis