KROHNE IFC 090 Converter EN User Manual
Page 26
4/7
F/R flow measurement
overranging
of outputs
}
dynamic response
of outputs, see Fct. 1.02
TIMECONST.:
I = I only
P = ALL
1.06
CONTROL B1
Control input B1 and B2 (see Fct. 3.07 HARDWARE)
1.07
CONTROL B2
• OFF
• EXT.RANGE (external range change)
Setting range: 5 - 80 PERCENT (= ratio of lower to upper range from
1:20 to 1:1.25. Value must be greater than that of Fct. 1.03 L.F. CUTOFF).
Press
↵
key to transfer to number setting.
• OUTP.HOLD (hold value of outputs)
• OUTP.ZERO (set outputs to “min.values“)
• TOTAL. RESET (reset totalizers)
• ERROR. RESET (delete error messages)
Press key
↵
to return to
Fct. 1.06 or 1.07 CONTROL B1 or B2.
Fct.
Text
Description and settings
1.06
PULS B1
Pulse output B1 (see Fct. 3.07 HARDWARE)
→
FUNCT. P
Select function for pulse output P
• OFF (switched off)
• 1 DIR. (1 flow direction)
• 2 DIR. (forward/reverse flow, F/R flow measurement)
Press key
↵
to transfer to subfunction
“SELECT P”.
→
SELECT P
Select pulse type
• PULSE/VOL. (pulses per unit volume, flowrate)
• PULSE/TIME (pulses per unit time for 100% flowrate)
Press key
↵
to transfer to subfunction
“PULSWIDTH”.
→
PULSWIDTH
Select pulse width
• 0.01 - 1.00 Sec (only for F
max
< 50 pulses/s)
• AUTO (automatic = 50% of the period duration
of the 100% output frequency)
• SYM. (symmetrical = pulse duty ratio 1:1 over total range)
Press key
↵
to transfer to subfunction
“VALUE P”.
→
VALUE P
Set pulse value per unit volume (appears only when
“PULSE/VOL.” set under “SELECT P” above)
• xxxx PulS/m3 • xxxx PulS/Liter • xxxx PulS/US.Gal
• xxxx PulS/ user-defined unit, factory-set is “Liter” or “US M.Gal” (see Fct. 3.05)
Setting range “xxxx” is dependent on the pulse width and the
full-scale range: P
min
= F
min
/ Q
100%
P
max
= F
max
/ Q
100%
Press key
↵
to return to
Fct. 1.06 “PULS. B1”.
→
VALUE P
Set pulse value per unit time (appears only when “PULSE/TIME”
set under “SELECT P” above)
• xxxx PulSe/Sec (=Hz) • xxxx PulSe/min • xxxx PulSe/hr
• xxxx PulSe/user-defined unit, factory-set is “hr” or “day” (see Fct. 3.05)
Setting range “xxxx” is dependent on the pulse width, see above
Press key
↵
to return to
Fct. 1.06 “PULS. B1”.
1.06
STATUS B1
Status output B1 and B2 (see Fct. 3.07 HARDWARE)
1.07
STATUS B2
• ALL ERROR
• FATAL ERROR
• OFF
• ON
• SIGN. I
• SIGN. P
}
• OVERFLOW I
• OVERFLOW P
}
• AUTO RANGE (automatic range change)
Setting range 5 - 80 PERCENT (= ratio of lower to upper range from
1:20 to 1:1.25. Value must be higher than that of Fct. 1.03 L.F. CUTOFF)
• TRIP POINT:
XXX
- YYY
XXX > YYY N/O contact
0 - 150% 0 - 150% XXX < YYY N/C contact
Hysteresis
≥
1%
(difference between XXX value and YYY value)
• EMPTY PIPE (signals that pipe is “empty”, only if option installed)
Press key
↵
to transfer to number setting.
Press key
↵
to return to
Fct. 1.06 or 1.07 STATUS B1
or
B2.