KROHNE IFC 090 Converter EN User Manual
Page 14
2/3
2.4 Status outputs B1 and B2 (terminals B1 / B
⊥
and B2 / B
⊥
)
• The status outputs are galvanically isolated from the current output and all input circuits.
• Setting data and functions can note down on page 0/3.
Please also refer to Sect. 3.2 “Factory settings” and Sect. 2.1 “Combinations of
binary outputs and inputs”, Fct. 3.07 HARDWARE.
• Typical status outputs B1 and B2
B2 status output B2
(or control input B2)
B
⊥
⊥
chassis ground, binary
outputs and inputs
B1 status output B1 (or pulse
output, control input)
Connection diagrams, see Sect. 2.6: diagrams 6 7 9 10 11
• Characteristics of the status outputs
Switch open
Switch closed
OFF (switched off)
no function
ON (e.g. operation indicator)
power OFF
power ON
SIGN I (F/ R mode)
Forward flow
Reverse flow
SIGN P (F/ R mode)
Forward flow
Reverse flow
TRIP POINT (limit switch)
inactive
active
AUTO RANGE (automatic range change) high range
low range
OVERFLOW I (I overranged)
current output OK
current output overranged
OVERFLOW. P (P overranged)
pulse output OK
pulse output overranged
ALL. ERROR (all errors)
errors
no error
FATAL.ERROR (fatal errors only)
errors
no error
EMPTY PIPE (option)
when measuring
when measuring
tube is empty
tube is full
• All operating data and functions can be set:
Display version:
IFC 090 D, see Sect. 4 and 5.8, Fct 1.06 or 1.07 for operator control
Basic version:
IFC 090 B, see Sect. 6.2 for operator control
• The status outputs can be operated in the active or passive mode.
Active mode:
The current output is the internal voltage source.
Passive mode:
External DC or AC voltage source required.