KROHNE IFC 090 Converter EN User Manual

Page 13

background image

2/2

Pulse output B1 (terminals B1 / B

) 2.3

• The pulse output is galvanically isolated from the current output and all input circuits.

• Setting data and functions can note down on page 0/3.

Please also refer to Sect. 3.2 “Factory settings” and Sect. 2.1 “Combinations of the
binary outputs and inputs”, Fct. 3.07 HARDWARE.

• Typical pulse output B1

• All operating data and functions can be set:

Display version:

IFC 090 D, see Sect. 4 and 5.7, Fct. 1.06 for operator control

Basis version:

IFC 090 B, see Sect. 6.2 for operator control

• The pulse output can be operated in the active or passive mode.

Active mode:

The current output is the internal voltage source,
connection of electronic totalizers (EC)

Passive mode:

External DC or AC voltage source required, connection of electronic (EC)
or electromechanical (EMC) totalizers

• Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or

cycle counters are connected, allow for minimum counting interval:

gate time, counter

1000

P

100%

[ Hz]

Connection diagrams, see Sect. 2.6: diagrams 3 4 5 9

B2 status output B2

or control input B2

B

chassis ground, binary
outputs and inputs

B1 pulse output B1 (or status

output, control input)