KROHNE IFC 090 Converter EN User Manual
Page 35
5/4
Current output I 5.6
Fct. 1.05 CURRENT I
Press
→
key.
→
FUNCT. I = Select function for current output,
press
→
key
•
OFF
(switched off, no function)
•
1 DIR.
(1 flow direction)
•
2 DIR.
(2 flow directions, F/R mode, forward/reverse)
Select using
↑
key.
Transfer to subfunction “RANGE I” with
↵
key.
Exceptions: When “OFF” selected, return to Fct. 1.05 CURRENT I.
When “2 DIR.”selected, transfer to subfunction “REV.RANGE”.
→
REV.RANGE = define full-scale range for reverse flow
(appears only when “2 DIR.” set under “FUNCT. I” above)
Press
→
key
•
100 PCT. (same full-scale value Q
100%
as forward flow, see Fct. 1.01)
•
PERCENT (settable range) Setting range 005 – 150% of Q
100%
(see Fct. 1.01)
Select with
↑
key.
Press
→
key to transfer to number setting.
Press
↵
key to transfer to subfunction “RANGE I”.
→
RANGE I = select measuring range,
press
→
key
•
0 - 20 mA
fixed ranges
•
4 - 20 mA
•
mA (user-defined value) I
0%
– I
100%
(value I
0%
< I
100%
!) 0-16 mA 4-20 mA
Press
→
key to transfer to number setting.
Select with key
↑
.
Press key
↵
to transfer to subfunction “I ERROR”.
→
I ERROR = set error value,
press
→
key
•
22 mA
(fixed value)
•
0.0 - I
0%
mA (variable value; only variable when I
0%
≥
1 mA, see ”RANGE I“ above)
Select using key
↑
. Press
→
key to transfer to number setting.
Press key
↵
to return to Fct. 1.05 CURRENT I.
Please refer to Sect. 3.2 “Factory settings”.
Refer to Sect. 2.6 for connection diagrams, and to Sect. 5.15 for characteristics.
}