KROHNE IFC 090 Converter EN User Manual
Page 12
2/1
Assignment of the binary outputs and inputs as required,
see 3.07 Fct. “HARDWARE” and Sect. 3.2 “Factory settings”.
Current output I
– active or passive mode
– internal power source for the binary outputs and inputs
Binary outputs/inputs
– terminal B1:
Terminals
pulse output B1
status output B1 or
control input B1
– terminal B2:
status output B2 or
control input B2
2.1 Combinations of outputs and inputs
2 Electrical connection of outputs and inputs
B1 B
⊥
⊥
B2 I+ I I
⊥
⊥
Binary outputs
and inputs
Current output
Output/input combinations 1) – 6)
Terminals: I+ / I / I
⊥
⊥
B1 / B
⊥
⊥
B2 / B
⊥
⊥
Combination:
1)
I
P
S
2)
I
P
C
3)
I
C
S
4)
I
S
C
5)
I
S1
S2
6)
I
C1
C2
I = current output
P = pulse output
S = status output
C = control input
2.2 Current output I
•
The current output is galvanically isolated from all input and output circuits.
•
Setting data and functions can note down on page 0/3.
Please also refer to Sect. 3.2 “Factory settings”.
•
Typical current output
•
All operating data and functions can be set.
•
Display version: IFC 090 D, see Sect. 4 and 5.6, Fct. 1.05 for operator control
Basic version: IFC 090 B, see Sect. 6.2 for operator control
•
The current output can also be used as an internal voltage source for the binary
outputs and inputs.
U
int
= 15 V DC I = 23 mA when operated without receiver instruments at the current output
I = 3 mA when operated with receiver instruments at the current output
•
Connection diagrams, see Sect. 2.6: diagrams 1 2 3 6 9 10 11
I+ approx. 15 V DC positive
voltage of current output
I current sink
I
⊥
chassis ground,
current output