KROHNE IFC 020 Converter EN User Manual
Page 28
Installation and operating instructions IFC 020
4/9
Fct.
Text
Description and settings
3.05
USER UNIT
Set any required unit for flowrate and counting
→
TEXT VOL.
Set text for required flowrate unit (max. 5 characters)
Factory-set: “Liter” or “MGal”.
Characters assignable to each place:
• A-Z, a-z, 0-9, or “ – “ (= blank character).
Press
↵
key to transfer to subfunction “FACT. VOL.”
→
FACT. VOL.
Set conversion factor (F
M
) for volume
Factory set “1.00000 E+3” for “Liter” or “2.64172E-4” for “US MGal”
(exponent notation, here: 1
x
10
3
or 2.64172
x
10
-4
).
Factor F
M
= volume per 1m
3
.
Setting range • 1.00000 E-9 to 9.99999 E+9 (= 10
-9
to 10
+9
)
Press
↵
key to transfer to subfunction “TEXT TIME”.
→
TEXT TIME
Set text for required time unit (max. 3 characters)
Factory-set: “hr” (=hour).
Characters assignable to each place:
• A-Z, a-z, 0-9, or “ – “ (= blank character).
Press
↵
key to transfer to subfunction “FACT. TIME”
→
FACT. TIME
Set conversion factor (F
T
) for time
Factory-set: “3.60000 E+3” for “hour” or “8.64000 E+4” for “day”
(exponent notation, here: 3.6
x
10
3
or 8.64
x
10
-4
).
Set factor F
T
in seconds.
Setting range
• 1.00000 E-9 to 9.99999 E+9 (= 10
-9
to 10
+9
)
Press
↵
key to return to Fct. 3.05 “USER UNIT”.
3.06
APPLICAT.
Set overload point for A/D converter
→
FLOW
• STEADY (150% of Q
100%
) • PULSATING (1000% of Q
100%
)
Press key
↵
to return to Fct. 3.06 “APPLICAT.“,
3.07
MEASURING POINT
Set measuring point no.
Factory setting: ALTOMETER
Characters assignable to each place:
• A-Z, a-z, 0-9, or “ – “ (= blank character).
Press
↵
key to return to Fct. 3.07 ”MEASURING POINT”
3.08
COM
Set comminucation interface
• OFF (switched off)
• HART (HART-interface switched on)
• KROHNE (RS 485 interface switched on)
• Address:”HART” 00-15 / “KROHNE” 000-239
• BAUD RATE: -1200
-2400
-4800
-9600
-19200
(appears with selection “KROHNE” only)
Press key
↵
to return to Fct. 3.08 “COM”.