Installation and operating instructions IFC 020

4/9

Fct.

Text

Description and settings

3.05

USER UNIT

Set any required unit for flowrate and counting

TEXT VOL.

Set text for required flowrate unit (max. 5 characters)

Factory-set: “Liter” or “MGal”.

Characters assignable to each place:

• A-Z, a-z, 0-9, or “ – “ (= blank character).

Press

key to transfer to subfunction “FACT. VOL.”

FACT. VOL.

Set conversion factor (F

M

) for volume

Factory set “1.00000 E+3” for “Liter” or “2.64172E-4” for “US MGal”

(exponent notation, here: 1

x

10

3

or 2.64172

x

10

-4

).

Factor F

M

= volume per 1m

3

.

Setting range • 1.00000 E-9 to 9.99999 E+9 (= 10

-9

to 10

+9

)

Press

key to transfer to subfunction “TEXT TIME”.

TEXT TIME

Set text for required time unit (max. 3 characters)

Factory-set: “hr” (=hour).

Characters assignable to each place:

• A-Z, a-z, 0-9, or “ – “ (= blank character).

Press

key to transfer to subfunction “FACT. TIME”

FACT. TIME

Set conversion factor (F

T

) for time

Factory-set: “3.60000 E+3” for “hour” or “8.64000 E+4” for “day”

(exponent notation, here: 3.6

x

10

3

or 8.64

x

10

-4

).

Set factor F

T

in seconds.

Setting range

• 1.00000 E-9 to 9.99999 E+9 (= 10

-9

to 10

+9

)

Press

key to return to Fct. 3.05 “USER UNIT”.

3.06

APPLICAT.

Set overload point for A/D converter

FLOW

• STEADY (150% of Q

100%

) • PULSATING (1000% of Q

100%

)

Press key

to return to Fct. 3.06 “APPLICAT.“,

3.07

MEASURING POINT

Set measuring point no.

Factory setting: ALTOMETER

Characters assignable to each place:

• A-Z, a-z, 0-9, or “ – “ (= blank character).

Press

key to return to Fct. 3.07 ”MEASURING POINT”

3.08

COM

Set comminucation interface

• OFF (switched off)

• HART (HART-interface switched on)

• KROHNE (RS 485 interface switched on)

• Address:”HART” 00-15 / “KROHNE” 000-239

• BAUD RATE: -1200

-2400

-4800

-9600

-19200

(appears with selection “KROHNE” only)

Press key