Installation and operating instructions IFC 020
4/6
Fct.
Text
Description and settings
1.04
DISPLAY
Display functions
→
DISP.FLOW
Select flow display
• NO DISP. • user unit, factory set is “Liter/hr” or “US MGal/day (see Fct. 3.05)
• m3/hr
• PERCENT
• Liter/Sec • BARGRAPH (value and bargraph display in %)
• US.Gal/min
Press
↵
key to transfer to subfunction “DISP. TOTAL.”.
→
DISP.TOTAL.
Select totalizer display
• NO DISP. (totalizer switched on but not displayed)
• OFF (totalizer switched off)
•
+
TOTAL
•
−
TOTAL
•
±
TOTAL
• SUM (
Σ
)
• ALL (single totalizer or all)
Press
↵
key to transfer to display unit
• m3
• Liter
• US.Gal
• user unit, factory set is “Liter” or “US MGal” (see Fct. 3.05).
Press
→
key to transfer to format setting.
Format setting
• Auto (exponent notation)
• # . #######
• ##### . ###
• ## . ######
• ###### . ##
• ### . #####
• ####### . #
• #### . ####
• ########
Press
↵
key to transfer to subfunction “DISP.MSG”.
→
DISP.MSG.
Additional messages required in measuring mode?
• NO
• YES (cyclic change with displays of measured values)
Press
↵
key to return to Fct. 1.04 DISPLAY.
1.05
CURRENT I
Current output I
→
FUNCT. I
Select function for current output I
• OFF (switched off)
• 1 DIR. (1 flow direction)
• 2 DIR. (forward/reverse flow, F/R flow measurement)
Press key
↵
, transfer to subfunction “RANGE I”;
→
RANGE I
Select measuring range
• 0 - 20 mA • 4 - 20 mA (fixed ranges)
• mA (user-defined range) I
0%
- I
100%
(Value I
0%
< I
100%
!) 0 - 16 mA 4 - 20 mA
To transfer to number setting, press key
→
!
Press key
↵
to transfer to subfunction “I ERROR“.
→
I ERROR
Select error value
• 22 mA • 0.0 to I
0%
mA (variable, see above if I
0%
> 1 mA)
To transfer to number setting, press key
→
!
Press key
↵
to revert to Fct. 1.05 CURRENT. I.