KROHNE IFC 020 Converter EN User Manual

Page 18

background image

Installation and operating instructions IFC 020

3/1

3 Start-up

Before powering the system, please check that it has been correctly installed according

to Sect. 1 and 2.

The flowmeter is delivered ready for operational use. All operating data have

been factory set in accordance with your specifications.

Please refer to Sect. 3.2 “factory settings”.

Power the unit, and the flowmeter will immediately start process flow measurement.

When powered, the display shows in succession: START UP and READY.

This is followed by display of the current flow rate and/or the current totalizer count

on either a continuous or alternating basis, depending on the setting under Fct. 1.04.

Refer to Sect. 4 and 5 for operator control of the “display version”.

3.1 Power-on and measurement

3.2 Factory setting

All operating data are factory set according to your order specifications.
If you have not made any particular specifications at the time of ordering, the instruments will be

delivered with the standard parameters and functions listed in the Table below.
To facilitate easy and rapid initial start-up, current output and pulse output are set to process flow

measurement in “2 flow directions”, so that the current flowrate is displayed and the volumetric

flow counted independent of the flow direction. On instruments equipped with a display, measured

values may possibly be shown with a “ – ” sign.
This factory setting for the current and pulse outputs may possibly lead to measuring errors,

particularly in the case of volume flow counting:
for example, if pumps are switched off and a “backflow” occurs which is not within the range of the

low-flow cutoff (SMU), or if separate displays and counts are required for both flow directions.
To avoid faulty measurements, therefore, it may be necessary to change the factory setting of

some or all of the following functions:

– low-flow cutoff SMU, Fct. 1.03, Sect. 5.3

– current output I, Fct. 1.05, Sect. 5.6

– pulse output P, Fct. 1.06, Sect. 5.7

– display (option), Fct. 1.04, Sect. 5.4
Operation see Section 4 and 5.

Standard factory settings

Function

Setting

1.01 Full-scale range Q

100%

see nameplate

1.02 Time constant

3 s, for I, S

and display

1.03 Low-flow

ON: 1 %

cutoff SMU

OFF: 2 %

1.04 Display (option)

flow rate

m

3

/hr or US Gal/min

totalizer(s)

m

3

or US Gal

1.05 Current output I

function

2 directions

range

4 - 20 mA

error message

22 mA

1.06 Pulse output P

function

2 directions

pulse value

1 pulse/s

pulse width

50 ms

1.07 Status output S

flow directions

Function

Setting

1.08 Control input

off

3.01 Language for display only English

3.02 Flowmeter

diameter

see nameplate

flow direction (see arrow

+ direction

on primary head)

}

3.04 Entry code

no

3.05 User unit

Liter/hror USMGal/day

3.06 Application

steady

3.07 Measuring point

Altometer

3.08 Communication interface off