7

TECHNICAL DATA

64

OPTIBAR DP 7060 C

www.krohne.com

04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en

Measuring accuracy

Differential pressure

Differential pressure

Differential pressure

Differential pressure

Reference conditions

acc. to IEC 60770-1

Ambient temperature (constant): +18...+30°C / +64...+86°F

Relative humidity (constant): 45...75%

Ambient pressure (constant): 860...1060 mbar / 12.5...15.4 psi

Mounting position: vertical

Rising characteristics

Measurement start at 0.00 bar / psi

Process diaphragm: 316 L / 1.4404

Fill fluid: silicone oil

Material of process flanges: 316 L / 1.4404

Power supply: 24 VDC ±3 VDC

Load for HART

®

: 250 Ω

Reference conditions

acc. to DIN EN 61298

Includes the non-linearity, hysteresis and repeatability under reference conditions Applies to
the digital interfaces (HART

®

, Profibus PA, Foundation Fieldbus) as well as for the analogue

4…20 mA current output.

[% of the set span]

TD < 5:1

TD > 5:1

TD < 10:1

TD > 10:1

30 mbar / 0.44 psi

< ±0.10%

< ± 0.02% x TD

100 mbar / 1.5 psi

-

-

< ±0.065%

<±-0.035% + 0.01% x TD

500 mbar / 7.3 psi

<±0.015% + 0.005% x TD

3 bar / 43.51 psi

16 bar / 232.1 psi

<±-0.035% + 0.01% x TD

Effect of ambient

temperature

Ambient temperature effect on zero and span in relation to the set measuring span. Applies to
the digital interfaces (HART

®

, Profibus PA, Foundation Fieldbus) as well as for the analogue

4…20 mA current output.

[% of the set span]

up to TD

-10...+60°C / +14...+140°F

-40...+85°C / -40...+185°F

30 mbar / 0.44 psi

30:1

<± 0.10% + 0.10% x TD

<± 0.15% + 0.15% x TD

100 mbar / 1.5 psi

100:1

<± 0.15% + 0.15% x TD

<± 0.15% + 0.20% x TD

500 mbar / 7.3 psi

<± 0.08% + 0.05% x TD

<± 0.12% + 0.06% x TD

3 bar / 43.51 psi

16 bar / 232.1 psi

<± 0.15% + 0.015% x TD

<± 0.15% + 0.20% x TD

Effect of system

pressure

Ambient temperature effect on zero point and span in relation to the set measuring span. Zero

point errors can be calibrated out under operating pressure. Applies to the digital interfaces
(HART

®

, Profibus PA, Foundation Fieldbus) as well as for the analogue 4…20 mA current

output.

[% of the set span]

up to nominal

pressure

on zero

on span

30 mbar / 0.44 psi

40 bar / 580 psi

<± 0.10% x TD

<± 0.10%

100 mbar / 1.5 psi

160 bar / 2320 psi

500 mbar / 7.3 psi

3 bar / 43.51 psi

16 bar / 232.1 psi

Effect of mounting

position

A position-dependent zero offset can be corrected.

≤0.1 mbar per 10° inclination