3.11.2 In closed vessels with gas-filled impulse lines

The following points should be observed in this application:

• Mount the differential pressure transmitter below the lower process connection so that the

impulse line is always filled with liquid.

• The low pressure side (L) must always be connected above the maximum level.
• For measurements of fluids with solid content, the installation of separators and drain valves

is recommended to enable collection and removal of debris and sediment.

Figure 3-9: Application example

1 Tank
2 Low-pressure line (L)
3 High-pressure line (H)
4 Differential pressure transmitter