Page 26

background image

3

INSTALLATION

26

OPTIBAR DP 7060 C

www.krohne.com

04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en

3.11 Measurement setup for level measurement

3.11.1 In open vessels with impulse line

The following points should be observed in this application:

• Mount the differential pressure transmitter below the lower process connection so that the

impulse lines are always filled with liquid.

• The low pressure side (L) is open to atmospheric pressure.
• For measurements in products with solid content, the installation of separators and drain

valves is recommended to enable collection and removal of debris and sediment.

Figure 3-8: Application example

1 Tank
2 Impulse line
3 Differential pressure transmitter