Start-up – KROHNE OPTIBAR DP 7060 C EN User Manual
Page 46
5
START-UP
46
OPTIBAR DP 7060 C
www.krohne.com
04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en
Sensor
mounting
correction
The mounting position of the device has a great impact on the measured value (offset), especially with
small measuring ranges and isolating systems. The sensor mounting correction compensates this
offset. The sensor mounting correction can automatically take on the current measured value as
correction value (auto correct). Alternatively, this correction value can also be manually entered using
the "Edit" function. Once the sensor mounting correction has taken place, the measured value is
corrected to 0. The sensor mounting correction can compensate a maximum of 20% of the nominal
range.
Offset
Input in adjustment unit, automatic transfer
of the current measured value
Adjustment
Adjustment refers to setting the zero point (zero) and maximum measured value (span). These values
correspond to the values of 4 and 20 mA. If the adjustment ranges are exceeded, the message
"Outside parameter limits" is displayed.
Distance
Density
Density
Density
Density
Distance in m (for kg/cm
3
) and ft (for lb/ft
3
)
Interface
Interface
Interface
Interface
Distance in mm, cm, m, in and ft
Min.-adjustment / Zero
Process pressure, differential pressure
Process pressure, differential pressure
Process pressure, differential pressure
Process pressure, differential pressure
Zero in %, pressure
Level and flow (standard 0%)
Level and flow (standard 0%)
Level and flow (standard 0%)
Level and flow (standard 0%)
Min. in X %, pressure or filling height
Density
Density
Density
Density
Min. in X %, density
Interface
Interface
Interface
Interface
Min. in X %, interface
Max.-adjustment / Span
Process pressure, differential pressure
Process pressure, differential pressure
Process pressure, differential pressure
Process pressure, differential pressure
Span in %, pressure
Level and flow (standard 100%)
Level and flow (standard 100%)
Level and flow (standard 100%)
Level and flow (standard 100%)
Min. in X %, pressure or filling height
Density
Density
Density
Density
Min. in X %, density
Interface
Interface
Interface
Interface
Min. in X %, interface
Damping
For the damping of process-dependent measured value fluctuations, you can choose a suitable
integration time. The values which can be entered are from 0 … 999 seconds with an increment of 0.1
seconds.
Integration time
In 0.1 second increments
Linearization
A linearization is necessary for all vessels in which the volume does not increase linearly with the
level height, e.g. in a horizontal cylindrical or spherical tank, and the indication or output of the
volume is required. Corresponding linearization curves are preprogrammed for these vessels. They
represent the correlation between the level percentage and vessel volume. By activating the
appropriate curve, the volume percentage of the vessel is displayed correctly. Enter the desired
parameters using the function buttons and save the entries. Note the following if the differential
pressure signal converter with corresponding approval is used as part of an overfill protection system
according to WHG (Water Resources Act): If a linearization curve is selected, the measuring signal is
no longer linearly proportional to the level. This must be taken into consideration by the user,
particularly when setting the switching point on the limit signal indicator.
Type of linearization
Level
Level
Level
Level
Linear, Horiz.cylinder, Sphere and User
programmable
The square of the flow is proportional to the pressure differential at the orifice plate or averaging pitot
tube:
q
2
~dp
To establish a linear relationship between flow rate and output variable, a square root extraction is
required: q~√dp
The differential pressure transmitter has this square root function. It is selected in menu item
"linearization curve". Enter the desired parameter using the appropriate keys and save your entries.
When selecting the "bi-directional square root" flow, the minimum adjustment must be entered with
a negative sign.
Type of linearization
Flow
Flow
Flow
Flow
Linear, To square root, Bi-directional linear,
Bi-directional square root and User
programmable
.book Page 46 Friday, May 2, 2014 10:25 AM