Start-up – KROHNE OPTIBAR DP 7060 C EN User Manual
Page 56
5
START-UP
56
OPTIBAR DP 7060 C
www.krohne.com
04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en
Out of specification
Maintenance required
Code
Text message
Cause
Action or description
S600
Inadmissible electronics
temperature
Temperature of the electronics in
the non-specified section
Check ambient temperature
Isolate electronics
Use device with higher
temperature range
S603
Inadmissible operating voltage
Operating voltage below specified
range
Check electrical connection - if
necessary, increase operating
voltage
Code
Text message
Cause
Action or description
M500
Error with the reset delivery
status
Saved reset delivery status is
incorrect
Send device for repair
M501
Error in the non-active
linearization table
Index markers are not
continuously rising, for example
illogical value pairs
Check linearisation table,
Delete table/Create new
M502
Error in the event memory
Hardware error in EEPROM
Exchange the electronics
Send device for repair
M504
Error on a device interface
Hardware defect
Check connections
Exchange the electronics
Send device for repair
M507
Error in the device settings
Error during setup
Error when carrying out a reset
Repeat setup,
Repeat reset
.book Page 56 Friday, May 2, 2014 10:25 AM