START-UP

5

47

OPTIBAR DP 7060 C

www.krohne.com

04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en

Current output

In the current output menu, the saturation region for above or below a threshold is set. Under

"Current output min./max." these limit values can be set. The factory setting is 3.8 mA and 20.5 mA.

This corresponds to the NAMUR recommendation NE 43.

Mode

Output characteristic

0...100% = 4...20 mA or

0...100% = 20...4 mA

Additional bi-directional flow:

20...4...20 mA or

4...20...4 mA

Failure mode

≤ 3.6 mA, ≥ 21 mA, last valid measured value

Min. and

Max.

Min. current

3.8 mA, 4 mA

Max. current

20.5 mA, 20 mA

Lock

adjustment /

Unlock

adjustment

In this menu item, a 4-digit PIN can be activated, which protects against undesirable or unintended

changes of the settings. With a PIN active, remote access via software or other systems is also no

longer possible.