beautypg.com

Installation – KROHNE OPTIBAR DP 7060 C EN User Manual

Page 28

background image

3

INSTALLATION

28

OPTIBAR DP 7060 C

www.krohne.com

04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en

3.11.3 In closed vessels with liquid / condensate filled impulse lines

The following points should be observed in this application:

• Mount the differential pressure transmitter below the lower process connection so that the

impulse lines are always filled with liquid.

• The low pressure side (L) must always be connected above the maximum level.
• For measurements of fluids with solid content, the installation of separators and drain valves

is recommended to enable collection and removal of debris and sediment.

Figure 3-10: Application example

1 Tank
2 Low-pressure line (L)
3 High-pressure line (H)
4 Differential pressure transmitter

.book Page 28 Friday, May 2, 2014 10:25 AM