5.4.5 Info
5.5 Reset
The reset function resets specific user entries. There are two reset functions available.
5.5.1 Delivery status
Restore the default values at the time of delivery, including the order-specific settings. A false
signal suppression, user programmable linearization curve as well as the measured value
memory will be deleted.
5.5.2 Basic settings
Reset the set data, including special parameters to the default values of the manufacturer. A
false signal suppression, user programmable linearization curve as well as the measured value
memory will be deleted.
The following menu items are affected during a reset
Flow element
charact.
In this menu item more information can be given on the primary elements used in the "flow"
application. This can be displayed as either flow or mass flow. The respective display and
adjustment units can then be selected accordingly.
Unit
Volume flow, Mass flow and User-defined
mbar, bar, Pa, kPa, MPa, psi, mmH2O, mmHg, inH2O, inHg and User-
defined
Adjustment
0 % = xxxx m
3
/h, 100 % = xxxx m
3
/h
Device name
Device name
Serial number
Instrument version
Software version
Hardware version
Factory calibration
Factory calibration date
Date of last change
Sensor characteristics Order-related device characteristics
Menu item
Parameter
Default
Measurement loop name
Sensor
Application
No reset
Unit
Adjustment units
mbar (cell ≤ 500 mbar)
bar (cell ≥ 1 bar)
Temperature unit
°
C
Sensor mounting correction
0.00 bar
Adjustment
Zero / Min. adjustment
0.00 bar - 0.00%
Span / Max. adjustment
+URL in bar - 100%
Damping
Integration time
0.0 seconds