Technical data, 2 technical data – KROHNE OPTIBAR DP 7060 C EN User Manual
Page 63

TECHNICAL DATA
7
63
OPTIBAR DP 7060 C
www.krohne.com
04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en
7.2 Technical data
INFORMATION!
•
The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.
•
Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Download Center).
Measuring system
Measuring principle
Piezoresistive differential pressure cell
Application range
•
Flow measurement (volume or mass flow) with corresponding differential pressure
transmitter in gases, vapours and liquids
•
Differential pressure measurement
•
Interface and density measurement
•
Level, volume and mass measurement of liquids
Measuring range
30 mbar...16 bar / 0.44...232 psi
Display and user interface
Display and user interface
Display and user interface
Display and user interface
Display on signal
converter
•
Dot-matrix display 45x27 mm / 1.77x1.06", illuminated
•
Display turnable in 90° steps
•
Digit size 13x7 mm / 0.51x0.27"
•
Ambient temperatures below -20°C / -4°F may affect the readability of the display
Display function
•
Measured value display or derived measured value such as filling height, density, interface
position, volume or mass flow and total counter
•
Warning and diagnostic information
•
All parameters are accessible via the operating menu
Operating and display
languages
German, English, French, Spanish, Portuguese, Italian, Dutch, Russian, Turkish, Polish and
Czech
Operation
Local operation via 4 push buttons on the display and adjustment module
Remote operation
•
PACTware
TM
, incl. Device Type Manager (DTM)
•
HART
®
Hand Held Communicator from Emerson Process
•
AMS
®
from Emerson Process
•
PDM
®
from Siemens
Integrated clock
Date format
Day / Month / Year
Time format
12 hours / 24 hours
Time zone
CET (Factory setting)
Rate deviation
Maximum 10.5 minutes / year
.book Page 63 Friday, May 2, 2014 10:25 AM