Start-up – KROHNE OPTIBAR DP 7060 C EN User Manual
Page 50
5
START-UP
50
OPTIBAR DP 7060 C
www.krohne.com
04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en
5.4.4 Additional adjustments
PIN
In this menu item the PIN can be changed. This option is only available if it has been enabled under
"Setup - Lock adjustment". The PIN is "0000" by default factory conditions.
0000
Change PIN
Date / Time
Internal clock setting
Write date, time, data in device
Reset
For further information refer to
Reset on page 51.
Factory settings, Basic settings, Totalizer 1 and Totalizer 2
Copy instrument
settings
For further information refer to
Saving the device settings on page 52.
Copy instrument settings
Special
parameters
Changing these settings is possible only after consultation with a service employee.
Scaling
In menu item "Scaling variable" you define the scaling variables and the scaling unit for the level
mode.
In menu item "Scaling format" you define the scaling format on the display and the scaling of the
level measurement for 0% and 100%.
Scaling variable
Scaling variable
Scaling unit
Scaling format
Scaling format
100% corresponds - user-defined value
0% corresponds - user-defined value
Current output
In this menu item it is determined which measured variable relates to which current output. Under
"Current output - Adjustment", the current output can be assigned a corresponding measured
value.
Current output
variable
For applications "Level"
Filling height or Pressure (Adjustment units), Static pressure, Percent,
Scaled, Linear percent, Meas. cell temp. and Electronics temperature
For applications "Differential pressure"
Differential pressure, Static pressure, Percent, Linear percent, Meas. cell
temp. and Electronics temperature
For applications "Flow"
Flow, Differential pressure, Static pressure, Pressure, Percent, Scaled,
Linear percent, Meas. cell temp. and Electronics temperature
For applications "Interface"
Interface height, Differential pressure, Percent, Scaled, Linear percent,
Meas. cell temp. and Electronics temperature
For applications "Density"
Density, Differential pressure, Percent, Scaled, Linear percent, Meas. cell
temp. and Electronics temperature
Current output,
adjustment
0% = 0% or 100% = 100%
HART
®
-Mode
The differential pressure transmitter offers the HART
®
modes "Analogue current output" and "Fix
current (4 mA). Under "Fix current (4 mA)", up to 64 sensors can be operated on a two-wire
multidrop mode. Each device must be assigned a HART
®
address between 0 und 63. The analogue
signal is fixed at 4 mA. Under "Analogue current output", however, a 4…20 mA signal can also be
issued for the assigned HART
®
address in multidrop mode.
HART
®
address
0...63
Output mode
Analogue current output with HART
®
or Fix current (4 mA) with HART
®