INSTALLATION

3

25

OPTIBAR DP 7060 C

www.krohne.com

04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en

3.10.2 In vapours and pure liquids

• Include the pressure tapping points to the side on the process line.
• The device must be mounted at the same height or underneath the tapping points.
• In steam applications, fill the impulse lines and/or condensate vessels with an appropriate

liquid.

Figure 3-7: Application example

1 Shut-off valve
2 Equalizing valve
3 Shut-off valve