Start-up, 6 saving the device settings – KROHNE OPTIBAR DP 7060 C EN User Manual

Page 52

background image

5

START-UP

52

OPTIBAR DP 7060 C

www.krohne.com

04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en

5.6 Saving the device settings

We recommended noting the parameters and archiving them afterwards. They are thus available
for multiple use or service purposes. If the pressure transmitter is equipped with a display and
adjustment module, the most important data can be read out of the sensor into the display and
adjustment module. The data remain there permanently even if the sensor power supply fails. If
it is necessary to exchange the signal converter, the display and adjustment module is inserted
into the replacement device and the data are written into the signal converter under the menu
item "Copy device data".

5.6.1 Copy device settings

This function allows you to upload the selected data to the display and adjustment module or
download selected data to the signal converter. This function serves as a backup of the data,
since it is retained even if the power fails.

The following settings are saved:

• all settings from the "Setup" and "Display" menus
• the menu items "Reset" and "Date/Time"
• Special parameters

Current output

Current output mode

Output characteristic 4...20 mA

Failure mode ≤ 3.6 mA

Current output variable

Linear percent - Level

Current output, adjustment

0...100% = 4...20 mA

Current output min./max.

Min. 3.8 mA

Max. 20.5 mA

Lock adjustment

Unlock

Language

English

Displayed value 1

Current output in %

Displayed value 2

Meas. cell temp. in °C

Backlight

Off

Simulation

Differential pressure

PIN

0000

Scaling

Scaling variable

Volume in L

Scaling format

0% = 0 L / 100% = 0 L

HART

®

mode

Address 0

Menu item

Parameter

Default

.book Page 52 Friday, May 2, 2014 10:25 AM