6.2.2. Results of "MAN" mode
M
Ω 05.06.01
Insulation Resistance
Voltage during the Test
Duration of the Test
Test mode
1.07
M
Ω
514V 15s
MAN 500V
Test voltage set
FUNC
VNOM
At the end of the test if
the Insulation
resistance is
lower
than R
MAX
(see Table2)
and the instrument
generated the
Nominal test Voltage,
the instrument emits a
double sound signal
indicating the positive
outcome of the test
and displays one
screen similar to the
screen alongside.
In order to evaluate the test you must compare the result with the limits indicated in the
Guidelines (see Table1).
The displayed result can be stored pressing the
SAVE key twice (according to
paragraph 9.1).
M
Ω 05.06.01
Maximum resistance value
which can be measured
(999
Ω is displayed if a
rated voltage of 500V was
selected see Table2).
The symbol
">" means that
the resistance value is
higher than R
MAX
.
> 999
M
Ω
523V 15s
MAN 500V
Test duration
FUNC
VNOM
If the Insulation
resistance is
higher
than R
MAX
(see Table2),
the instrument emits a
double sound signal at
the end of the test
indicating the positive
outcome of the test
and displays one screen
similar to the screen
alongside.
The displayed result can be stored pressing the
SAVE key twice (according to
paragraph 9.1).