Sirius89n, En - 102 – HT instruments SIRIUS89N User Manual
Page 104

SIRIUS89N
EN - 102
CURRENT MEASUREMENT with FlexINT clamps - 3000A range
Range (A)
Voltage input
Resolution
Accuracy
30.0
÷ 999.9
2.55mV
÷ 84.99mV
8.5
µV
±(1.0%rdg + 17µV)
1000
÷ 3000
85.0mV
÷ 255mV
85
µV
±(0.5% rdg + 85µV)
1A = 85
µV ; Rinput = 400kΩ
POWER MEASUREMENT – SINGLE PHASE SYSTEM (AUTORANGE)
Quantity Range
Accuracy
MAX
Resolution
ACTIVE POWER
0
÷ 999.9W
1
÷ 999.9kW
1
÷ 999.9MW
1000
÷ 9999MW
0.1W
0.1kW
0.1MW
1MW
REACTIVE POWER
0
÷ 999.9VAR
1
÷ 999.9kVAR
1
÷ 999.9MVAR
1000
÷ 9999MVAR
0.1VAR
0.1kVAR
0.1MVAR
1MVAR
APPARENT POWER
0
÷ 999.9VA,
1
÷ 999.9kVA,
1
÷ 999.9MVA
1000
÷ 9999MVA
0.1VA
0.1kVA
0.1MVA
1MVA
ACTIVE ENERGY
(Classe2 EN61036)
0
÷ 999.9Wh,
1
÷ 999.9kWh,
1
÷ 999.9MWh
1000
÷ 9999MWh
0.1Wh
0.1kWh
0.1MWh
1MWh
REACTIVE ENERGY
(Classe3 IEC1268)
0
÷ 999.9VARh,
1
÷ 999.9kVARh,
1
÷ 999.9MVARh
1000
÷ 9999MVARh
±(1.0%Reading+2digit)
0.1VARh
0.1kVARh
0.1MVARh
1MVARh
Cos
ϕ MEASUREMENT – SINGLE PHASE SYSTEM
Cos
ϕ
Resolution Accuracy
[°]
0.20
ч 0.50
1.0
0.50
ч 0.80
0.7
0.80
ч 1.00
0.01
0.6
VOLTAGE AND CURRENT HARMONICS MEASUREMENT – SINGLE PHASE SYSTEM
Range
Accuracy Resolution
DC – 25H
±(5% rdg + 2 digit)
26H – 33H
±(10% rdg + 2 digit)
34H – 49H
±(15% rdg + 2 digit)
0.1V / 0.1A
Harmonics values are null under fixed threshold:
- DC: its values is null if it is < 2%of Fundamental or is <2% of Full Scale clamp
- 1
st
Current Harmonic: its values is null if it is < 0.2% Full Scale clamp
- 2
nd
÷ 49
th
: its values is null if it is < 2% of fundamental or is <2% of Full Scale clamp
ENVIRONMENTAL PARAMETER MEASUREMENT
Range
Accuracy
Resolution
-20°C –80 °C
0.1 °C
0
÷ 100% UR
0.1% UR
0.001Lux
÷ 20.00 Lux
0.001
÷ 0.02 Lux
0.1Lux
÷ 2000 Lux
0.1
÷ 2 Lux
1Lux
÷ 20 kLux
±(2% rdg + 2dgt)
1
÷ 20 Lux
LEAKAGE CURRENT MEASUREMENT
Range (*)
Resolution [mA]
Accuracy
Input Impedance
Overload Protection
0.5
÷ 999.9mA
0.1mA
±(5% rdg + 2digit)
400k
Ω 5V
(*): During a recording the instrument detect only Current > 5mA with Resolution 1mA