VOLTAGE MEASUREMENT (RCD, LOOP, PHASE ROTATION)
Range [V]
Resolution [V]
Accuracy
0
÷ 460V
1
±(3%Reading + 2digit)
LOOP P-P, P-N: LINE IMPEDANCE MEASUREMENT (Phase – Phase, Phase - Neutral)
Range [
Ω] Resolution
[
Ω]*
Accuracy
0.01
ч 9.99
10.0
ч 199.9
0.01
0.1
±(5% Reading + 3digit)
(*) 0.1 m
Ω on range 0.0 ÷ 199.9 mΩ (with IMP57)
Peak value of the Test current
127V
3.65A
230V
6.64A
400V
11.5A
Voltage Range (Phase – Phase, Phase – Neutral)
100
ч250/100ч440V
Frequency 50Hz
± 0.5Hz
LOOP P-PE: FAULT LOOP IMPEDANCE MEASUREMENT (Phase - Earth)
Range [
Ω] Resolution
[
Ω]*
Accuracy
0.01
ч 19.99
20.0
ч 199.9
200
ч 1999
0.01
0.1
1
±(5% Reading + 3digit)
(*) 0.1 m
Ω on range 0.0 ÷ 199.9 mΩ (with IMP57)
Peak value of the Test current:
127V
3.65A
230V 6.64A
Voltage Range (Phase –Earth)
100
÷250V
Frequency 50Hz
± 0.5Hz
LOOP R
a 15mA
: FAULT LOOP IMPEDANCE MEASUREMENT without RCD Tripping (Phase - Earth)
Range [
Ω] Resolution
[
Ω]
Accuracy
1
÷ 1999
1
- 0%, +(5% Reading + 3digit)
Test Current
15mA
Voltage Range (Phase –Earth)
100
÷250V 50Hz
EARTH: GROUND RESISTANCE MEASUREMENT WITH EARTH RODS
Range RE [
Ω]
Resolution [
Ω]
Accuracy
0.01 – 19.99
20.0 – 199.9
200 - 1999
0.01
0.1
1
±(5% Reading + 3 digit)
Test Current
<10mA – 77.5Hz
Open circuit Test Voltage
<20V RMS
RESISTIVITY MEASUREMENT
Range
ρ
Resolution
Accuracy
0.60
÷19.99 Ωm
20.0
÷ 199.9Ωm
200
÷ 1999Ωm
2.00
÷ 99.99kΩm
100.0
÷ 125.6kΩm(*)
0.01
Ωm
0.1
Ωm
1
Ωm
0.01 k
Ωm
0.1 k
Ωm
±(5% Reading + 3 digit)
(*) setting distance = 10m
Test Current
<10mA – 77.5Hz
Open circuit Test Voltage
<20V RMS
14.1.2. ANALYZER and AUX functions
VOLTAGE MEASUREMENT – SINGLE PHASE SYSTEM (AUTORANGE)
Range [V]
Resolution [V]
Accuracy
Input Impedance
15
÷ 310V
0.2V
310
÷ 600V
0.4V
±(0.5%
Reading+2digit)
300k
Ω (Phase-Neutral)
300k
Ω (Phase-Phase)
VOLTAGE SAG AND SURGE DETECTION – SINGLE PHASE SYSTEM (MANUAL RANGE)
Range [V]
Resolution
(Voltage)
Resolution
(Time)
Accuracy
(Voltage)
Accuracy (rif. 50Hz)
(Time)
Input Impedance
15
÷ 310V
0.2V
30
÷ 600V
0.4V
10ms (½ period)
±(1.0% rdg +2 digit)
± 10ms (½ period)
300k
Ω (Phase-Neutral)
300k
Ω (Phase-Phase)
CURRENT MEASUREMENT with FlexEXT and STD clamps – SINGLE PHASE SYSTEM (AUTORANGE)
Range [V] (*)
Resolution [mV]
Accuracy
Input Impedance
Overload Protection
0.005
÷0.26V 0.1
0.26
÷1V 0.4
±(0.5%rdg +2digit)
400k
Ω
5V
(*): Example: with a 1000A/1V full scale clamp , the instrument detect only current higher than 5A
CURRENT MEASUREMENT with FlexINT clamps - 1000A range
Range (A)
Voltage input
Resolution
Accuracy
10.0
÷19.9
950.0
µV ÷ 1.691mV
±(4.0% rdg + 8.5µV)
20.0
÷ 99.9
1.7mV
÷ 8.491mV
±(1.0% rdg + 8.5µV)
100.0
÷ 999.9
8.5mV
÷ 84.99mV
8.5
µV
±(1.0% rdg + 8.5µV)
1A = 85
µV ; Rinput = 400kΩ