HT instruments SIRIUS89N User Manual
Page 18

SIRIUS89N
EN - 16
6.1.3. Results of "AUTO" mode
LOW
Ω 05.06.01
Average resistance value
(
Ravg)
Resistance values and
corresponding test current
got exchanging the
polarities of test leads
1.05Ω
R+ R-
1.07
Ω 1.03Ω
219mA 219mA
AUTO 0.11
Ω
FUNC
CAL
At the end of the test, if
the
average resistance
value Ravg is lower
than 5
Ω the instrument
emits a
double sound
signal indicating the
positive outcome of
the test and displays
one screen similar to the
screen alongside.
The displayed result can be stored pressing the
SAVE key twice (according to
paragraph 9.1).
6.1.4. Results of "RT+" and "RT-" modes
LOW
Ω 05.06.01
Max Resistance value of
R+ or R-.
Test current
Duration of the Test
1.07Ω
219mA
RT+ 0.11
Ω TIME: 10s
FUNC
CAL
↑
↓
if a
resistance value
RT+ or RT+ lower than
5
Ω is detected, the
instrument emits a
double sound signal
indicating the positive
outcome of the test
displays one screen
similar to the screen
alongside.
Note:
We recommend to use crocodiles and to check if the crocodiles make a good
contact with the conductor under test. Indeed in this test the instrument gives as
final result the maximum measured value of R+ or R- and suing test leads
instead of crocodiles could give you faulty result due to faulty contact between
the test leads and conductor under test
The displayed result can be stored pressing the
SAVE key twice (according to
paragraph 9.1).