Auto-configure – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 79
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
79
Master Programming Level
Programming
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen
with technical information about the selected module.
In the technical information screen, pressing 1 for Type will display the following screens:
Press the number corresponding to the module type, if any, that is installed with the selected
address. This will enable the module.
Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically
program the device type and address into the system. Pressing 3 while viewing ANN-BUS Screen
#1 will begin the Auto-Configure process and cause the following screen to be displayed:
NOTE: When the Secondary ANN-BUS is enabled through System Setup programming, addresses
1 - 3 will be on the primary ANN-BUS and addresses 4 - 8 will be on the seconary ANN-BUS.
ANN-BUS MODULE TYPE
1=NONE
2=ANN-80
3=ANN-I/O
Module Type Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen