Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 55
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
55
Master Programming Level
Programming
The following examples show the editing of Input Zone 1:
Enable/Disable Zone
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the zone will be disabled by the control panel, preventing the circuit from reporting alarms
and troubles to the panel. The control panel LCD will display the zone which has been disabled
and FACP will turn on the Trouble indicator.
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:
INPUT ZONE 1
1=ENABLED YES
2=TYPE 2-WIRE SMOKE
Edit Input Zone Screen #2
Edit Input Zone Screen #3
INPUT ZONE 1
1=OUTPUT CIRCUIT MAP
1 3
2=FREEZE SUPV. NO
Edit Input Zone Screen #4
INPUT ZONE 1
1=ADJECTIVE/NOUN
2=DESCRIPTION
QQQQQQQQQQQQQQQQQQQQ
INPUT ZONE
1=ENABLED
2=TYPE
Edit Input Zone Screen #2
ZONE 1 TYPE
1=PULL STATION
2=MANUAL RELEASE
3=MANUAL REL/ABORT
Zone Type Screen #1