Template 11: Agent/Waterflow - Cross-Zone
FACP Configuration Templates
Device Installation Example for Template 11
Notes:
1. All End-of-Line Resistors, illustrated in this example, are 4.7K
, ½ watt (PN: 71252).
2. All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to “CAC-5X Class A Converter Module” on page 31.
TB5
TB4
TB7
TB6
OUT1 OUT2
OUT3 OUT4
B
+
B
-
1 1
B
+
B
-
2 2
B
+
B
-
3 3
B
+
B
-
1 1
B
+
B
-
6 6
+ - + -
+ - + -
+ - + - + - + - + -
+ -
B
-
5
B
+
B
-
3 3
B
+
B
-
2 2
B
+
B
-
4 4
B
+
B
-
4 4
+
+
+
+
+
+
Input Circuit #1
2-Wire Smoke
Input Circuit #3
Manual Release/Abort Sw. Combo
Input Circuit #4
Discharge Pressure
Input Circuit #5
Waterflow
Output
Circuit #1
Release
Solenoid 1
Output
Circuit #3
Alarm
NAC
Input Circuit
#6
Supervisory
Output
Circuit #4
Release
Stage
Coded
Input Circuit #2
2-Wire Smoke
ag
ent
tem
p1
1.
wm
f
Output
Circuit #2
Release
Solenoid 2