Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 68
68
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
Programming
Master Programming Level
This screen allows the programmer to view the cross-zoned grouping for Release Circuit 1 or
Release Circuit 2. In the following example, Template 1 has been chosen as the FACP
Configuration [refer to“FACP CONFIG (Application Templates)” on page 53]. Pressing 1 for
Release 1 will display the following screen:
The display indicates that Input Zone 1 is cross-zoned with Input Zone 2. Both of these zones
active at the same time will cause Release Circuit 1 to activate.
The user can alter the cross-zoning by pressing the number key corresponding to the Zone to be
reprogrammed. Screens similar to the following will be displayed:
In this example, since the cross-zoning for Release Circuit 1 (Zone 1) is being displayed, Yes is
shown for Zone 1 which is cross-zoned with Zone 2. Zone 2 displays Yes since it is cross-zoned
with Zone 1. Zone 3 displays No for no cross-zoning. Zone 4 displays N/A since it is an Abort
Switch. Zone 5 displays No for cross-zoning. Zone 6 is a supervisory and displays N/A. By
pressing the number key corresponding to the desired zone, the display for that zone will toggle
between Yes and No indicating cross-zoning to Zone 1 or no cross-zoning to Zone 1.
Note that zones programmed as supervisory cannot be cross-zoned and will therefore indicate N/A.
REL 1 CROSS GROUPS
1= X 1 2
2= NONE
3= NONE
REL 1 CROSS GROUP 1
1=ZONE 1 YES
2=ZONE 2 YES
3=ZONE 3 NO
Select Cross Zone Screen #1
REL 1 CROSS GROUP 1
1=ZONE 4 N/A
2=ZONE 5 NO
3=ZONE 6 N/A
Select Cross Zone Screen #2